TYPICAL SPECIFICATIONS |
Model: |
SIBD-CA |
|
Description: |
Fan shall be of the "Square in-line" type with a square inlet and outlet. Fan shall be
designed for floor mount or hung installations in-line with ducting, and have a belt driven
centrifugal wheel. Fan shall be a corrosion resistant steel, belt driven,
square inline blower.
|
|
Application: |
Square In-Line Duct Blowers are suitable for various applications. Commonly mounted indoors with both
inlet and outlet ducts to supply or exhaust air. Square In-Line Duct Blowers are engineered to discharge
air, fumes and other contaminants horizontally in a duct.
|
|
Certifications: |
Square In-line Duct Blower(s) shall be licensed to bear the AMCA Certified Ratings Seal for
Air and Sound Performance and be ETL Listed to UL705 Standards.
|
|
Construction: |
Square In-line Duct Blower(s) shall be constructed of steel. A removable cover shall provide
blower motor access, and drive access shall be provided on both sides through removable panels.
Blowers shall be belt driven; centrifugal backward inclined, with cast iron pillow block,
regreaseable ball bearings having a minimum L50 (average) life of 200,000 hours. The shaft
shall be keywayed at both ends.
Drives are to be selected for 150% of driven horsepower. Blower pulley shall be fixed,
machined, cast iron. Motor pulley shall be cast iron, variable speed.
|
Housing |
The blower shell shall be constructed of heavy-gauge galvanized steel. Side panels shall be
removable for service access.
|
|
Wheel |
Backward inclined non-overloading, all-aluminum wheel. Balanced in accordance with AMCA
standard 204-96, Balance Quality and Vibration Levels for Fans.
|
|
Motor & Motor Compartment |
Motor shall have permanently lubricated ball bearings and be of voltage, phase, and enclosure
as specified. A motor cover shall be supplied as standard.
|
|
Shaft and Bearings |
Shafts shall be precision ground and polished. Bearings, selected specifically for air handling duty,
and of the pillow block relubricatable type, shall be selected to have a predicted L10 life of not
less than 200,000 hours at maximum cataloged operating speed.
|
|
Belts & Drives |
Belts and drives shall be sized for a minimum of 150% of the driven BHP. Drives shall be of cast iron and keyed to the shafts.
|
|
Product: Fan
shall be model SIBD-CA as manufactured by CaptiveAire Systems.
|
|
|