Performance Table |
CFM | Static Pressure in Inches W.G. |
---|
0.000 | 0.250 | 0.500 | 0.750 | 1.000 | 1.250 | 1.500 | RPM Sone/BHP | RPM Sone/BHP | RPM Sone/BHP | RPM Sone/BHP | RPM Sone/BHP | RPM Sone/BHP | RPM Sone/BHP |
6000 | 171 2.9 / 0.16 | 272 6.4 / 0.63 | | | | | |
9000 | 256 6.0 / 0.54 | 331 7.8 / 1.16 | 394 9.7 / 1.92 | 446 11.3 / 2.73 | 494 12.7 / 3.59 | | |
12000 | 341 8.1 / 1.29 | 400 9.9 / 2.06 | 453 11.5 / 2.97 | 500 12.9 / 3.98 | 543 13.9 / 5.02 | 582 15.0 / 6.10 | 619 16.7 / 7.21 |
15000 | 426 10.6 / 2.50 | 475 12.2 / 3.46 | 519 13.4 / 4.50 | 561 14.3 / 5.66 | 600 15.8 / 6.89 | | |
18000 | 511 13.2 / 4.33 | 554 14.2 / 5.47 | 591 17.0 / 6.65 | | | | |
21000 | 596 20 / 6.88 | | | | | | |
|
Performance shown is certified for installation type A: Free inlet, Free outlet.
Performance ratings do not include the effects of appurtenances in the airstream.
Power rating (BHP) does not include transmission losses. The sound ratings shown are loudness
values in fan sones at 5 ft (1.5m) in a hemispherical free field calculated per AMCA
Standard 301. Values shown are for Installation Type A: free inlet fan sone levels.
|