Performance Table |
CFM | Static Pressure in Inches W.G. |
---|
0.000 | 0.250 | 0.500 | 0.750 | 1.000 | 1.500 | 2.000 | 2.500 | 3.000 | RPM Sone/BHP | RPM Sone/BHP | RPM Sone/BHP | RPM Sone/BHP | RPM Sone/BHP | RPM Sone/BHP | RPM Sone/BHP | RPM Sone/BHP | RPM Sone/BHP |
1500 | 856 4.5 / 0.11 | 1014 6.0 / 0.19 | 1157 7.5 / 0.29 | 1292 9.6 / 0.40 | 1420 10.6 / 0.53 | 1661 13.4 / 0.80 | 1877 16.4 / 1.10 | 2075 19.3 / 1.41 | 2256 21 / 1.73 |
2000 | 1142 7.9 / 0.25 | 1264 8.5 / 0.37 | 1376 9.4 / 0.49 | 1484 10.5 / 0.62 | 1587 11.5 / 0.75 | 1787 15.1 / 1.06 | 1978 18.0 / 1.41 | 2157 20 / 1.77 | |
2500 | 1426 11.3 / 0.49 | 1527 10.8 / 0.63 | 1620 11.9 / 0.78 | 1710 12.9 / 0.93 | 1796 13.9 / 1.09 | 1962 17.1 / 1.43 | 2126 19.8 / 1.80 | | |
3000 | 1711 15.4 / 0.85 | 1797 13.9 / 1.02 | 1877 15.1 / 1.19 | 1953 16.8 / 1.36 | 2028 18.9 / 1.55 | 2172 20 / 1.93 | | | |
3500 | 1997 20 / 1.34 | 2071 19.4 / 1.54 | 2141 19.2 / 1.74 | 2208 19.6 / 1.94 | | | | | |
4000 | 2282 24 / 2.00 | | | | | | | | |
|
Performance shown is certified for installation type B: Free inlet, Ducted outlet.
Performance ratings do not include the effects of appurtenances in the airstream.
Power rating (BHP) includes transmission losses. The sound ratings
shown are loudness values in sones at 5 ft (1.5m) in a
hemispherical free field calculated per AMCA Standard 301.
Values shown are for Installation Type B: free inlet fan sone levels.
Ratings do not include the effect of duct end correction.
|