Performance Table |
CFM | Static Pressure in Inches W.G. |
---|
0.000 | 0.250 | 0.500 | 0.750 | 1.000 | 1.500 | 2.000 | 2.500 | 3.000 | RPM Sone/BHP | RPM Sone/BHP | RPM Sone/BHP | RPM Sone/BHP | RPM Sone/BHP | RPM Sone/BHP | RPM Sone/BHP | RPM Sone/BHP | RPM Sone/BHP |
2000 | 705 7.5 / 0.14 | 818 8.4 / 0.24 | 924 9.7 / 0.36 | 1021 11.1 / 0.48 | 1111 12.5 / 0.61 | 1275 15.2 / 0.91 | 1423 17.2 / 1.23 | 1560 19.0 / 1.57 | 1686 21 / 1.92 |
2500 | 881 9.3 / 0.27 | 972 10.3 / 0.40 | 1060 11.4 / 0.54 | 1145 12.5 / 0.68 | 1224 14.5 / 0.83 | 1371 16.5 / 1.16 | 1506 18.3 / 1.51 | 1632 20 / 1.89 | 1751 22 / 2.29 |
3000 | 1057 12.0 / 0.47 | 1133 12.3 / 0.63 | 1208 13.2 / 0.79 | 1281 14.2 / 0.95 | 1351 15.2 / 1.12 | 1484 17.8 / 1.48 | 1608 19.8 / 1.87 | 1724 22 / 2.28 | 1834 24 / 2.72 |
3500 | 1233 14.5 / 0.75 | 1298 14.4 / 0.93 | 1363 15.5 / 1.11 | 1427 16.5 / 1.30 | 1489 17.6 / 1.49 | 1609 19.9 / 1.89 | 1722 22 / 2.31 | 1830 24 / 2.76 | |
4000 | 1409 17.1 / 1.12 | 1466 17.5 / 1.33 | 1523 18.3 / 1.53 | 1579 19.3 / 1.75 | 1635 20 / 1.96 | 1744 22 / 2.40 | 1848 24 / 2.86 | | |
4500 | 1586 20 / 1.59 | 1636 21 / 1.82 | 1686 21 / 2.06 | 1737 22 / 2.30 | 1787 23 / 2.53 | | | | |
5000 | 1762 24 / 2.18 | 1807 23 / 2.44 | 1761 23 / 2.17 | 1898 25 / 2.96 | | | | | |
5500 | 1938 27 / 2.90 | | | | | | | | |
|
Performance shown is certified for installation type B: Free inlet, Ducted outlet.
Performance ratings do not include the effects of appurtenances in the airstream.
Power rating (BHP) includes transmission losses. The sound ratings
shown are loudness values in sones at 5 ft (1.5m) in a
hemispherical free field calculated per AMCA Standard 301.
Values shown are for Installation Type B: free inlet fan sone levels.
Ratings do not include the effect of duct end correction.
|