Performance Table |
CFM | Static Pressure in Inches W.G. |
---|
0.000 | 0.250 | 0.500 | 0.750 | 1.000 | 1.500 | 2.000 | 2.500 | 3.000 | RPM Sone/BHP | RPM Sone/BHP | RPM Sone/BHP | RPM Sone/BHP | RPM Sone/BHP | RPM Sone/BHP | RPM Sone/BHP | RPM Sone/BHP | RPM Sone/BHP |
3800 | 910 11.0 / 0.48 | 998 11.0 / 0.71 | 1078 12.6 / 0.94 | 1153 14.2 / 1.18 | 1223 15.9 / 1.44 | 1356 19.8 / 1.98 | 1481 21 / 2.58 | 1599 23 / 3.22 | 1711 24 / 3.90 |
4400 | 1054 13.7 / 0.74 | 1131 13.0 / 1.00 | 1202 15.4 / 1.27 | 1269 17.2 / 1.54 | 1333 18.8 / 1.83 | 1454 21 / 2.42 | 1568 22 / 3.07 | 1677 24 / 3.75 | 1781 25 / 4.47 |
5000 | 1197 16.7 / 1.09 | 1266 15.8 / 1.39 | 1330 18.7 / 1.69 | 1391 20 / 1.99 | 1450 21 / 2.30 | 1561 22 / 2.96 | 1666 24 / 3.65 | 1766 25 / 4.37 | |
5600 | 1341 19.9 / 1.53 | 1403 18.3 / 1.86 | 1461 21 / 2.20 | 1517 22 / 2.54 | 1571 22 / 2.88 | 1673 24 / 3.59 | 1770 25 / 4.33 | | |
6200 | 1485 22 / 2.07 | 1541 20 / 2.45 | 1594 21 / 2.82 | 1646 23 / 3.19 | 1695 24 / 3.57 | 1790 25 / 4.33 | | | |
6800 | 1628 25 / 2.74 | 1679 23 / 3.14 | 1729 24 / 3.55 | 1777 25 / 3.96 | 1822 26 / 4.36 | | | | |
7400 | 1772 29 / 3.53 | 1819 27 / 3.97 | 1865 28 / 4.41 | 1910 33 / 4.86 | | | | | |
8000 | 1916 33 / 4.46 | 1959 34 / 4.93 | | | | | | | |
|
Performance shown is certified for installation type B: Free inlet, Ducted outlet.
Performance ratings do not include the effects of appurtenances in the airstream.
Power rating (BHP) includes transmission losses. The sound ratings
shown are loudness values in sones at 5 ft (1.5m) in a
hemispherical free field calculated per AMCA Standard 301.
Values shown are for Installation Type B: free inlet fan sone levels.
Ratings do not include the effect of duct end correction.
|