Performance Table |
CFM | Static Pressure in Inches W.G. |
---|
0.000 | 0.250 | 0.500 | 0.750 | 1.000 | 1.500 | 2.000 | 2.500 | RPM Sone/BHP | RPM Sone/BHP | RPM Sone/BHP | RPM Sone/BHP | RPM Sone/BHP | RPM Sone/BHP | RPM Sone/BHP | RPM Sone/BHP |
4500 | 501 6.7 / 0.32 | 584 8.6 / 0.58 | 667 10.3 / 0.89 | 742 12.1 / 1.22 | 813 13.5 / 1.57 | 948 17.5 / 2.36 | 1076 22 / 3.22 | |
5500 | 612 10.5 / 0.59 | 679 12.0 / 0.89 | 750 12.4 / 1.24 | 816 14.1 / 1.62 | 878 15.4 / 2.02 | 995 19.0 / 2.89 | 1106 22 / 3.83 | 1214 26 / 4.84 |
6500 | 724 13.6 / 0.98 | 778 14.7 / 1.32 | 839 14.2 / 1.72 | 898 15.9 / 2.14 | 954 18.0 / 2.59 | 1059 21 / 3.54 | 1158 24 / 4.56 | |
7500 | 835 15.9 / 1.50 | 881 16.5 / 1.89 | 933 16.4 / 2.33 | 986 18.5 / 2.80 | 1037 20 / 3.30 | 1133 23 / 4.34 | | |
8500 | 946 18.7 / 2.18 | 987 19.9 / 2.62 | 1031 20 / 3.10 | 1077 21 / 3.61 | 1124 23 / 4.16 | | | |
9500 | 1058 22 / 3.05 | 1093 23 / 3.53 | 1132 23 / 4.05 | 1173 24 / 4.61 | | | | |
10500 | 1169 25 / 4.11 | 1201 26 / 4.64 | | | | | | |
|
Performance shown is certified for installation type B: Free inlet, Ducted outlet.
Performance ratings do not include the effects of appurtenances in the airstream.
Power rating (BHP) includes transmission losses. The sound ratings
shown are loudness values in sones at 5 ft (1.5m) in a
hemispherical free field calculated per AMCA Standard 301.
Values shown are for Installation Type B: free inlet fan sone levels.
Ratings do not include the effect of duct end correction.
|