RDUS-U2-CA Specification
Print Print

TYPICAL SPECIFICATIONS
Model: RDUS-U2-CA

 
Description: Fans shall be RDUS-U2-CA restaurant duty utility set.

Fans shall be designed for maximum efficiency. Fans shall have a sharply rising pressure characteristic extending through the operating range and continuing to rise well beyond the efficiency peak to assure quiet and stable operation under all conditions. Horsepower characteristics shall be truly self-limiting and shall reach a peak in the normal selection area.


 
Application: RDUS-U2-CA for exhausting grease-laden air from kitchens, restaurants, cooking and dishwasher hoods. The heavy-duty construction of RDUS-U2-CA fans also makes them suitable for high heat and high static pressure applications.

 
Certifications:     Fan shall be ETL listed to UL705, and ULC-S645 Standards.

 
Construction:  
Housing
Housings shall be welded steel throughout. Inlets shall be fully streamlined. Housings shall be suitably braced to prevent vibration or pulsation. Totally enclosed weather cover shall enclose the motor, motor sheave and V-belt drives. Model RDUS-U2-CA shall include 1 wheel cleanout door for inspection and maintenance of the wheel and a 2" drain.

Wheel
Fan wheels shall have die-formed single thickness blades designed for maximum efficiency, and quiet and stable operation. Blades shall be continuously welded to the back plate and wheel cone. Wheels shall be statically and dynamically balanced and the complete fan assembly including motor and drive shall be test balanced at or near the operating speed at the factory prior to shipment.

Motor & Motor Compartment
Motor shall have permanently lubricated ball bearings and be of voltage, phase, and enclosure as specified. A weather/motor cover shall be supplied as standard.

Shaft and Bearings
Shafts shall be AISI 1040 or 1045 hot rolled steel, accurately turned, ground, polished, and ring gauged for accuracy. Shafts shall be sized for the first critical speed of at least 1.43 times the maximum speed.

Bearings shall be heavy duty, grease lubricated, anti-friction ball or roller, self-aligning, pillow block type and selected for a minimum L-50 life of 200,000 hours at the maximum fan RPM.


Belts & Drives
Motor sheaves shall be cast iron, variable pitch on applications 10 HP and smaller, and fixed pitch on 15 HP and larger.

Product: Fan shall be model RDUS-U2-CA as manufactured by CaptiveAire Systems.