Electric Heater Formulas
|
|
Conversion
|
1 KW = 3413 BTU
|
|
|
Load Requirement
|
KW = |
|
CFM x Temp. Rise
|
3160
|
|
|
|
Line Current (1 Phase)
|
|
|
|
Line Current (3 Phase)
|
Amps = |
|
KW x 1000
|
Volts x 1.73
|
|
|
|
Applied vs. Rated KW Factors
|
Rated Voltage |
Applied Voltage |
120 |
208 |
220 |
230 |
240 |
277 |
440 |
460 |
480 |
120 |
1.00 |
3.00 |
3.36 |
3.67 |
4.00 |
5.33 |
13.44 |
14.69 |
16.00 |
208 |
.33 |
1.00 |
1.12 |
1.22 |
1.33 |
1.77 |
4.47 |
4.89 |
5.32 |
220 |
.30 |
.89 |
1.00 |
1.09 |
1.19 |
1.58 |
4.00 |
4.37 |
4.76 |
230 |
.27 |
.82 |
.91 |
1.00 |
1.09 |
1.45 |
3.66 |
4.00 |
4.36 |
240 |
.25 |
.75 |
.84 |
.92 |
1.00 |
1.33 |
3.36 |
3.67 |
4.00 |
277 |
.19 |
.56 |
.63 |
.69 |
.75 |
1.00 |
2.52 |
2.76 |
3.00 |
440 |
.07 |
.22 |
.25 |
.27 |
.30 |
.40 |
1.00 |
1.09 |
1.19 |
460 |
.07 |
.20 |
.23 |
.25 |
.27 |
.36 |
.91 |
1.00 |
1.09 |
480 |
.06 |
.19 |
.21 |
.23 |
.25 |
.33 |
.84 |
.92 |
1.00 |
|
1. Locate Heater Rated Voltage.
|
2. Locate Actual Applied Voltage.
|
3. Multiply Heater Rated KW by Factor Shown to Obtain Actual KW Capacity
|