Typical Installation
|
|
|
- CYLINDER CONTROL UNIT: Integral design requires no separate release
pressure cylinder- separate wire cable activation lines for automatic fusible link and
optional remote pull station provide an added measure of safety - an easily
accessible manual release mechanism which provides an option to the automatic
fusible link and, depending on local codes, can be used in place of a remote manual
pull station - unique fool proof technique for achieving necessary input wire cable
tension.
- PIPING: Unbalanced piping network simplifies application design and installation -
no separate piping to connect system pressure cylinders to extinguishing agent
container. Schedule 40 stainless,chrome-plated and black pipe can be used.
- CYLINDERS:(DOT-4BW-225 Rated) - Contain Pyro-Chem Potassium Carbonate
Solution stored at 225 psi - pressure gauge for visual maintenance checks - 3.00
and 4.60 gallon sizes provide 10 and 15 flow point coverage respectively,
offering a broad range of application coverage.
- NOZZLES: Fixed and Swivel head nozzles have been established to relax
placement tolerances.
- REMOTE MANUAL PULL STATION: Simple operating instructions with a double
action release avoids careless system discharge - a 150' wire cable run with 1/16
inch cable and 40 corner pulleys maximum - a dedicated wire cable input line to the
cylinder control head provides a true back-up in the event fusible links are fouled.
- FUSIBLE LINK KITS: Accommodates both series and terminal placement to
minimize inventory and simplify ordering - all necessary components included for
efficient assembly and installation - a 350° F fusible link standard - other
temperatures available - 20 fusible links on a 150' wire cable run with 40 corner
pulleys maximum provides substantial hazard coverage.
- AUTOMATIC GAS SHUT-OFF VALVE: Complies with requirements pertaining to
the shut-off of fuel as described by NFPA 17A - after regular maintenance/service
check can be reset at control head for convenience of service technician - a 100' wire
cable run with 30 corner pulleys maximum provides mounting flexibility.
- CORNER PULLEYS AND ACCESSORIES: Designed to ensure reliable system
function, as tested by Underwriters Laboratories.
|