AM-BSA-N Series
|
|
Water Wash Low Proximity Exhaust Ventilator
|
AquaMatic's ETL Listed AM-BSA-N is a low proximity exhaust ventilator
with an automatic internal water wash system.
The AM-BSA-N is a Type 1, wall mounted exhaust canopy utilizing high velocity
slot type grease extraction with an automatic internal water wash system, and
integrated wash and rinse cycles.
|
|
|
- ETL Listed and ETL Sanitation Listed Product
- Automatic Internal Water Wash System
- Choice of Electromechanical or Solid State Programmable Control Panels
- Superior Exhaust Flow Rates
- Exceptional Capture andContainment of Cooking Vapors
- Wall Configuration
- 100% Type 304 Stainless Steel Construction
- Front Exposed Corners Ground andPolished to Match Grain of Ventilator
- Grease Extracting Cartridges
- Grease Drain System
- Removable Access Doors for Exhaust Plenum Access
- Pre-punched Hanging Angles
- Integral Stainless Steel Double End Panels
|
|
|
AM-2 Control Panel provides push button operation with relay control of
the exhaust and make-up air fans as well as the cleaning cycle of the ventilator.
The time period of the rinse cycle is adjustable up to 3 minutes. The control
panel includes a combination pressure/temperature gauge, shock absorber,
pressure reducing valve, water solenoid valve, detergent pump, line strainer,
and gate valve. See product specification sheet for details.
TAC-3000 Control Panel is a state-of-the-art, 24 hour, seven day, solid state
water wash control panel. Featured is its' four line liquid crystal display and
user-friendly menu driven programming. Door mounted indicator lights show the
status of supply and exhaust fans, fire condition, water valve, and AC power.
Buttons on the stainless steel door are used to control the programming and are
touch sensitive with no moving parts. It is capable of controlling up to 5 wash
zones independently with user selected durations and delay time between washings
as well as controlling the fan ON and OFF times.
|
|
|
- Fire Suppression System
- Back Supply Air Plenum
- Dry Slot with No Internal Wash System
- Cold Water Mist
- ETL Listed Exhaust Fire Damper
- Enclosure Panels to Ceiling
- Roof Top Packages
- Exhaust Fans
- Make-Up Air Units:
-- Untempared Units
-- Direct Gas Fired Heated Units
-- Indirect Gas Fired Heated Units
-- Electric Heated Units
-- Heating & Cooling Coils
|
|
|
AquaMatic� offers a total system to insure maximum installation and operating
efficiencies. Components consist of the ventilator, fire system and electrical
controls contained within an integral utility cabinet, and fan packages including
exhaust, untempered and tempered make-up air packages. Also available are air
purification and energy management systems. Fire suppression systems include
final hookup and inspection. Call your AquaMatic Representative for more details.
|
|
|
600�F - Ovens, Steamers, Kettles,
Open-Burner Ranges, Griddles, Fryers, Gas Charbroilers, Electric Charbroilers
|
Single Wall Hood
2 Wall Hoods Back-to-Back |
250
500 |
Exhaust Based on 1500 FPM
Supply Based on 800 FPM |
|
|
|
Application
The ventilator shall provide flexibility in designing kitchen ventilation
equipment and shall be tested and listed for use over light, medium and heavy
duty cooking surfaces, maximum 600�F.
Construction
The ventilator shall be 100% constructed of Type 304 stainless steel
with #3 or #4 polish. All seams shall be welded or in conformance with
ETL standards. Front exposed corners shall be ground and polished to
match the ventilator grain. Individual component construction shall be
determined by manufacturer and ETL. Construction shall be dependent
on the structural application to minimize distortion and other defects.
All seams, joints and penetrations of the ventilator where grease-laden
vapors and exhaust gases are present, must be liquid-tight, continuous
welds in accordance with NFPA 96.
The ventilator shall be constructed to include:
- A full length, horizontal exhaust inlet slot
and a series of fixed baffles for grease removal.
- An integral drain system on the ventilator back.
Multiple end-to-end ventilators can be manifolded to one common drain.
- Exhaust duct collar 5" high with 1" flange.
- A minimum of four connections for hanger rods.
Connectors shall have 9/16" holes pre-punched in 1 1/2" x 1 1/2" angle iron at
the factory to allow for hanger rod connection by others.
- Heavy duty, removable grease extracting cartridge,
with size and quantity determined by the hood's dimensional parameters,
not to exceed 60" in length.
Certifications
The ventilator shall be ETL Listed as "Exhaust Hoods Without Exhaust Damper", ETL Listed to
Canadian Safety Standards, ETL Sanitation Listed and built in accordance with NFPA 96.
Documentation
Manufacturer shall furnish complete computer generated submittal drawings
including ventilator section view(s), plan view(s), duct sizing, and CFM
and static pressure requirements. Static pressure, air velocity and air
volume requirements indicated on drawings shall be precise and accurate
and ventilator shall preform to said specifications. Drawings shall be
available to the engineer, architect and owner for their use in
construction, operation and maintenance.
|
|
|
The AM-BSA-N Model has been certified by ITS. This certification mark indicates that
the product has been tested to and has met the minimum requirements of a widely recognized
(consensus) U.S. and Canadian products safety standard, that the manufacturing site
has been audited, and that the applicant has agreed to a program of periodic factory
follow-up inspections to verify continued performance.
|
|
|
Models AM-BSA-N are ETL Listed under file number 3054804-001 and complies with UL710, ULC710 and ULC-S646 Standards.
|
|
|