Performance Table |
CFM | Static Pressure in Inches W.G. |
---|
0.000 | 0.250 | 0.500 | 0.750 | 1.000 | 1.250 | 1.500 | RPM Sone/BHP | RPM Sone/BHP | RPM Sone/BHP | RPM Sone/BHP | RPM Sone/BHP | RPM Sone/BHP | RPM Sone/BHP |
1000 | 1038 4.7 / 0.07 | 1236 6.1 / 0.13 | 1397 7.6 / 0.20 | 1534 11.6 / 0.26 | 1658 12.3 / 0.33 | 1779 13.1 / 0.41 | 1898 13.2 / 0.49 |
1200 | 1246 6.1 / 0.13 | 1415 9.0 / 0.20 | 1562 13.0 / 0.27 | 1690 14.0 / 0.35 | 1805 14.8 / 0.43 | | |
1400 | 1454 11.6 / 0.20 | 1598 13.9 / 0.28 | 1735 15.3 / 0.37 | 1854 16.4 / 0.45 | | | |
1600 | 1661 15.0 / 0.30 | 1788 16.3 / 0.39 | 1912 16.0 / 0.49 | | | | |
1800 | 1869 17.8 / 0.43 | | | | | | |
|
Performance shown is for installation type A: Free inlet, Free outlet.
Performance ratings do not include the effects of appurtenances in the airstream.
Power rating (BHP) does not include drive losses. The sound ratings shown are loudness
values in fan sones at 5 ft (1.5m) in a hemispherical free field calculated per AMCA
Standard 301. Values shown are for Installation Type A: free inlet fan sone levels.
|