Performance Table |
CFM | Static Pressure in Inches W.G. |
---|
0.000 | 0.250 | 0.500 | 0.750 | 1.000 | 1.500 | 2.000 | 2.500 | RPM Sone/BHP | RPM Sone/BHP | RPM Sone/BHP | RPM Sone/BHP | RPM Sone/BHP | RPM Sone/BHP | RPM Sone/BHP | RPM Sone/BHP |
800 | 1110 6.4 / 0.09 | 1286 8.1 / 0.15 | 1429 9.3 / 0.21 | 1562 10.7 / 0.28 | 1688 11.8 / 0.35 | 1928 14.0 / 0.51 | 2145 15.9 / 0.67 | 2353 18.2 / 0.86 |
1000 | 1387 8.9 / 0.17 | 1536 10.3 / 0.24 | 1661 11.5 / 0.32 | 1773 12.5 / 0.40 | 1880 13.3 / 0.48 | 2088 15.4 / 0.66 | 2283 17.4 / 0.85 | |
1200 | 1664 11.9 / 0.29 | 1794 13.2 / 0.38 | 1905 13.5 / 0.47 | 2003 14.2 / 0.56 | 2098 15.2 / 0.65 | 2277 17.1 / 0.85 | | |
1400 | 1942 14.5 / 0.46 | 2056 15.7 / 0.56 | 2154 16.1 / 0.66 | 2244 17.4 / 0.77 | 2329 18.2 / 0.88 | | | |
1600 | 2219 18.0 / 0.68 | 2322 19.5 / 0.80 | 2413 20 / 0.92 | | | | | |
1800 | 2497 22 / 0.97 | | | | | | | |
|
Performance shown is certified for installation type B: Free inlet, Ducted outlet.
Performance ratings do not include the effects of appurtenances in the airstream.
Power rating (BHP) includes transmission losses. The sound ratings
shown are loudness values in sones at 5 ft (1.5m) in a
hemispherical free field calculated per AMCA Standard 301.
Values shown are for Installation Type B: free inlet fan sone levels.
Ratings do not include the effect of duct end correction.
|