Performance Table
CFMStatic Pressure in Inches W.G.
0.0000.2500.5000.7501.0001.5002.000
RPM
Sone/BHP
RPM
Sone/BHP
RPM
Sone/BHP
RPM
Sone/BHP
RPM
Sone/BHP
RPM
Sone/BHP
RPM
Sone/BHP
2500470
5.6 / 0.10
605
5.7 / 0.26
734
8.0 / 0.45
851
9.7 / 0.68
   
3000563
7.6 / 0.18
678
7.1 / 0.35
787
9.0 / 0.56
893
10.5 / 0.81
991
12.5 / 1.08
  
3500657
9.8 / 0.28
757
9.2 / 0.48
851
10.1 / 0.71
944
11.5 / 0.97
1034
13.3 / 1.27
1201
16.9 / 1.89
 
4000751
12.4 / 0.42
840
9.9 / 0.65
923
11.4 / 0.89
1005
13.0 / 1.17
1086
14.5 / 1.48
1241
17.7 / 2.16
1384
22 / 2.89
4500845
12.5 / 0.59
925
11.3 / 0.85
999
12.6 / 1.12
1072
14.4 / 1.42
1145
15.8 / 1.74
1288
18.9 / 2.45
 
 
5000939
14.3 / 0.81
1012
15.8 / 1.10
1079
14.1 / 1.39
1145
15.4 / 1.71
1211
16.9 / 2.04
1341
21 / 2.79
 
 
55001032
16.2 / 1.08
1100
17.7 / 1.39
1162
15.8 / 1.71
1222
17.2 / 2.05
1282
18.5 / 2.41
 
 
 
60001126
18.2 / 1.41
1189
19.8 / 1.75
1246
17.6 / 2.09
1302
18.9 / 2.45
1357
20 / 2.82
 
 
 
65001220
21 / 1.79
1279
22 / 2.16
1332
23 / 2.53
1384
23 / 2.91
 
 
  
70001314
23 / 2.23
1369
25 / 2.63
 
 
 
 
   
75001408
27 / 2.75
 
 
     
Performance shown is certified for installation type B:  Free inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances in the airstream. Power rating (BHP) includes transmission losses. The sound ratings shown are loudness values in sones at 5 ft (1.5m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for Installation Type B: free inlet fan sone levels. Ratings do not include the effect of duct end correction.