Performance Table |
CFM | Static Pressure in Inches W.G. |
---|
0.000 | 0.250 | 0.500 | 0.750 | 1.000 | 1.500 | 2.000 | RPM Sone/BHP | RPM Sone/BHP | RPM Sone/BHP | RPM Sone/BHP | RPM Sone/BHP | RPM Sone/BHP | RPM Sone/BHP |
6000 | 408 7.5 / 0.38 | 481 9.7 / 0.72 | 548 9.5 / 1.10 | 613 10.7 / 1.53 | 674 13.0 / 2.01 | | |
8000 | 543 12.0 / 0.89 | 600 13.3 / 1.34 | 653 12.2 / 1.81 | 704 13.8 / 2.31 | 754 16.3 / 2.85 | 848 19.0 / 4.03 | 937 22 / 5.37 |
10000 | 679 15.8 / 1.74 | 725 16.8 / 2.30 | 768 15.6 / 2.88 | 811 16.3 / 3.47 | 852 17.8 / 4.08 | 932 23 / 5.39 | 1009 26 / 6.82 |
12000 | 815 18.7 / 3.01 | 853 19.9 / 3.68 | 890 21 / 4.36 | 926 20 / 5.05 | 962 22 / 5.76 | 1031 25 / 7.24 | |
14000 | 951 24 / 4.77 | 983 25 / 5.55 | 1016 27 / 6.34 | 1047 28 / 7.14 | | | |
16000 | 1086 30 / 7.12 | | | | | | |
|
Performance shown is certified for installation type B: Free inlet, Ducted outlet.
Performance ratings do not include the effects of appurtenances in the airstream.
Power rating (BHP) includes transmission losses. The sound ratings
shown are loudness values in sones at 5 ft (1.5m) in a
hemispherical free field calculated per AMCA Standard 301.
Values shown are for Installation Type B: free inlet fan sone levels.
Ratings do not include the effect of duct end correction.
|