Performance Table |
CFM | Static Pressure in Inches W.G. |
---|
0.000 | 0.250 | 0.500 | 0.750 | 1.000 | 1.500 | 2.000 | RPM Sone/BHP | RPM Sone/BHP | RPM Sone/BHP | RPM Sone/BHP | RPM Sone/BHP | RPM Sone/BHP | RPM Sone/BHP |
10000 | 359 9.2 / 0.68 | 413 10.2 / 1.23 | 465 12.1 / 1.88 | 514 13.9 / 2.59 | 560 15.8 / 3.36 | 653 20 / 5.06 | |
12000 | 431 12.4 / 1.18 | 475 14.3 / 1.82 | 521 15.4 / 2.54 | 564 17.1 / 3.34 | 604 17.8 / 4.20 | 681 22 / 6.04 | 759 26 / 8.05 |
14000 | 503 18.2 / 1.87 | 540 20 / 2.60 | 579 19.8 / 3.41 | 618 20 / 4.29 | 654 21 / 5.23 | 723 24 / 7.25 | 789 27 / 9.41 |
16000 | 574 22 / 2.80 | 607 23 / 3.62 | 641 23 / 4.51 | 675 25 / 5.47 | 709 26 / 6.49 | 772 27 / 8.67 | |
18000 | 646 26 / 3.98 | 675 27 / 4.90 | 705 28 / 5.88 | 736 28 / 6.92 | 766 29 / 8.01 | | |
20000 | 718 30 / 5.46 | 743 31 / 6.48 | 770 33 / 7.55 | 798 34 / 8.67 | 826 35 / 9.84 | | |
22000 | 790 34 / 7.27 | 813 35 / 8.39 | 837 38 / 9.55 | | | | |
24000 | 862 43 / 9.44 | | | | | | |
|
Performance shown is certified for installation type B: Free inlet, Ducted outlet.
Performance ratings do not include the effects of appurtenances in the airstream.
Power rating (BHP) includes transmission losses. The sound ratings
shown are loudness values in sones at 5 ft (1.5m) in a
hemispherical free field calculated per AMCA Standard 301.
Values shown are for Installation Type B: free inlet fan sone levels.
Ratings do not include the effect of duct end correction.
|