Performance Table |
RPM | Tip Speed | Motor HP | Static Pressure in Inches W.G. |
---|
0.000 | 0.125 | 0.250 | 0.375 | 0.500 | 0.625 | 0.750 | 1.000 | 1.250 | CFM Sone/BHP | CFM Sone/BHP | CFM Sone/BHP | CFM Sone/BHP | CFM Sone/BHP | CFM Sone/BHP | CFM Sone/BHP | CFM Sone/BHP | CFM Sone/BHP |
1050 | 3788 | 0.50 | 1461 5.3 / 0.13 | 1330 5.2 / 0.13 | 1189 5.2 / 0.13 | 1010 5.2 / 0.13 | 787 5.3 / 0.13 | 512 5.3 / 0.13 | | | |
1150 | 4149 | 0.50 | 1600 6.3 / 0.17 | 1482 6.0 / 0.17 | 1353 6.0 / 0.17 | 1209 6.0 / 0.17 | 1029 6.0 / 0.17 | 823 6.3 / 0.17 | 560 6.3 / 0.17 | | |
1250 | 4510 | 0.50 | 1739 7.3 / 0.21 | 1633 6.9 / 0.21 | 1514 6.9 / 0.21 | 1395 6.9 / 0.21 | 1243 6.9 / 0.21 | 1063 6.9 / 0.21 | 876 7.3 / 0.21 | | |
1350 | 4871 | 0.50 | 1878 8.3 / 0.27 | 1781 7.7 / 0.27 | 1672 7.7 / 0.27 | 1562 7.7 / 0.27 | 1438 7.7 / 0.27 | 1292 7.7 / 0.27 | 1117 7.7 / 0.27 | 722 8.4 / 0.27 | |
1450 | 5231 | 0.50 | 2017 9.4 / 0.33 | 1926 8.5 / 0.33 | 1827 8.5 / 0.33 | 1725 8.5 / 0.33 | 1623 8.5 / 0.33 | 1495 8.5 / 0.33 | 1356 8.5 / 0.33 | 1029 9.6 / 0.33 | |
1550 | 5592 | 0.50 | 2156 10.6 / 0.41 | 2071 10.6 / 0.41 | 1981 9.3 / 0.41 | 1884 9.3 / 0.41 | 1789 9.3 / 0.41 | 1684 9.3 / 0.41 | 1561 9.3 / 0.41 | 1269 9.3 / 0.41 | 947 10.8 / 0.41 |
1650 | 5953 | 0.50 | 2296 14.3 / 0.49 | 2216 12.1 / 0.49 | 2133 11.6 / 0.49 | 2042 11.4 / 0.49 | 1952 11.2 / 0.49 | 1863 11.0 / 0.49 | 1755 10.8 / 0.49 | 1512 10.5 / 0.49 | 1220 10.2 / 0.49 |
|
Performance shown is certified for installation type B: Free inlet, Ducted outlet.
Performance ratings do not include the effects of appurtenances in the airstream.
Speed (RPM) shown is nominal. Performance is based on the actual speed of the test.
The sound ratings shown are loudness values in sones at 5 ft (1.5m) in a
hemispherical free field calculated per AMCA Standard 301.
Values shown are for Installation Type B: free inlet fan sone levels.
|