Performance Table |
CFM | Static Pressure in Inches W.G. |
---|
0.000 | 0.125 | 0.250 | 0.375 | 0.500 | 0.625 | RPM Sone/BHP | RPM Sone/BHP | RPM Sone/BHP | RPM Sone/BHP | RPM Sone/BHP | RPM Sone/BHP |
8000 | 365 8.8 / 0.25 | 450 12.2 / 0.54 | 545 15.8 / 0.95 | 618 19.5 / 1.39 | 678 23 / 1.89 | 730 26 / 2.43 |
10000 | 456 12.9 / 0.49 | 518 15.3 / 0.79 | 599 18.4 / 1.26 | 673 17.8 / 1.78 | 734 23 / 2.33 | 788 28 / 2.90 |
12000 | 547 17.0 / 0.84 | 595 20 / 1.17 | 658 12.9 / 1.66 | 727 17.5 / 2.26 | 789 22 / 2.88 | |
14000 | 638 24 / 1.33 | 677 26 / 1.68 | 727 28 / 2.19 | 785 17.6 / 2.83 | | |
16000 | 729 30 / 1.98 | 762 31 / 2.37 | 803 34 / 2.89 | | | |
|
Performance shown is certified for installation type A: Free inlet, Free outlet.
Performance ratings do not include the effects of appurtenances in the airstream.
Power rating (BHP) does not include transmission losses. The sound ratings shown are loudness
values in fan sones at 5 ft (1.5m) in a hemispherical free field calculated per AMCA
Standard 301. Values shown are for Installation Type A: free inlet fan sone levels.
|