MUA RE-CIRCULATION SPRAY/BAKE SEQUENCE

"SPRAY"
POWER ON LIGHT ENERGIZED
  • IF EQUIPPED, MAKE-UP AIR UNIT’S DAMPER (INTAKE OR DISCHARGE) IS ENERGIZED; END SWITCH ON DAMPER ACTUATOR IS MADE WHEN DAMPER IS 75% OPEN

START DELAY TIMER ENERGIZED
  • IF EQUIPPED WITH EXHAUST FAN STARTERS, HIGH SPEED STARTER FOR TWO SPEED EXHAUST MOTORS IS ENERGIZED OR BOTH EXHAUST FAN MOTOR STARTERS FOR TWO SINGLE SPEED EXHAUST FANS
  • IF EQUIPPED WITH EXHAUST AUTO BALANCE SYSTEM, VFD IS ENABLED AND STATIC PRESSURE CONTROLLER OVERRIDDEN TO FORCE EXHAUST FAN VFD TO HIGH SPEED

START DELAY TIMER TIMES OUT
  • MAKE-UP AIR UNITS SUPPLY FAN STARTER ENERGIZED.
  • AFTER AIRFLOW IS PROVEN "BLOWER LIGHT" IS ENERGIZED
  • RE-CIRCULATION SYSTEMS MODULATION DAMPERS ARE IN 100% OUTSIDE AIR MODE
  • IF EQUIPPED WITH AUTO BALANCE SYSTEM, STATIC PRESSURE CONTROLLER CONTROLS EXHAUST FAN VFD BASED UPON BOOTH PRESSURE REQUIREMENTS
  • SPRAY LIGHT ENERGIZED
  • BURNER ENABLED VIA THE MANUAL "HEAT ON/OFF" SWITCH
  • "BURNER LIGHT" ENERGIZED IF HEAT IS "ON"
  • SET POINT ONE ENABLED ON "M" SERIES TEMPERATURE CONTROLLER

"BAKE"
PURGE CYCLE TIMER ENERGIZED
  • PURGE LIGHT ENERGIZED
  • NO CHANGE IN MAKE UP AIR UNIT OR EXHAUST FAN OPERATION
PURGE CYCLE TIMER TIMES OUT
BAKE TIMER ENERGIZED
  • RE-CIRCULATION SYSTEMS (80/20) DAMPER POSITIONING MANUAL POTENTIOMETER IS ENABLED AND DAMPERS ADJUSTS TO POTENTIOMETERS SETTING.
  • BURNER IS ENABLED
  • "BURNER LIGHT" ENERGIZED
  • IF EQUIPPED WITH EXHAUST STARTERS, LOW SPEED STARTER ENERGIZED FOR TWO SPEED EXHAUST MOTOR OR ONE EXHAUST FAN STARTER IS DE-ENERGIZED ON TWO SINGLE SPEED EXHAUST FAN SYSTEMS
  • IF EQUIPPED WITH EXHAUST AUTO BALANCE SYSTEM, STATIC PRESSURE CONTROLLER CONTROLS EXHAUST FAN VFD BASED UPON BOOTH PRESSURE REQUIREMENTS
  • BAKE LIGHT ENERGIZED
  • SET POINT TWO ENABLED ON "M" SERIES TEMPERATURE CONTROLLER
  • BOOTH LIGHTS LOCKED OUT
BAKE CYCLE TIMES OUT
COOL DOWN TIMER ENERGIZED
  • COOL DOWN LIGHT ENERGIZED
  • RE-CIRCULATION SYSTEMS (80/20) MODULATION DAMPERS ARE IN 100% OUTSIDE AIR MODE
  • BURNER ENABLED VIA THE MANUAL "HEAT ON/OFF" SWITCH
  • "BURNER LIGHT" ENERGIZED IF HEAT IS "ON"
  • IF EQUIPPED WITH EXHAUST FAN STARTERS, HIGH SPEED STARTER FOR TWO SPEED EXHAUST MOTORS IS ENERGIZED OR BOTH EXHAUST FAN MOTOR STARTERS FOR TWO SINGLE SPEED EXHAUST FANS
  • IF EQUIPPED WITH EXHAUST AUTO BALANCE SYSTEM, VFD IS ENABLED AND STATIC PRESSURE CONTROLLER OVERRIDDEN TO FORCE EXHAUST FAN VFD TO HIGH SPEED
  • SET POINT ONE ENABLED ON "M" SERIES TEMPERATURE CONTROLLER

COOL DOWN CYCLE COMPLETE
MAKE UP AIR UNIT AND EXHAUST SYSTEM SHUTS OFF
BOOTH LIGHTS ENERGIZED