Thermostatic Control Option Specification |
|
|
TYPICAL SPECIFICATIONS |
Model: |
Thermostatic Control Option |
|
Description: |
The Electrical Package, typically FP, is designed to thermostatically activate the exhaust fans
for an exhaust hood whenever elevated temperatures are sensed in the exhaust system. This option
will meet the requirements of IMC 507.2.1.1 by providing a thermostat(s) mounted in the duct or
hood riser to sense increased exhaust temperatures.
|
|
|
Controls shall be listed by ETL (UL 508A). The control enclosure shall be NEMA 1 rated and listed
for installation inside of the exhaust hood utility cabinet. The control enclosure may be constructed
of stainless steel or painted steel.
|
|
|
Temperature probes(s) located in the duct riser shall be constructed of Stainless Steel. The thermostat
is factory set at an activation temperature of 85 degrees. Once the exhaust temperature reaches the
set-point, then contacts will be closed and the exhaust fans will be activated. The controls also provide
hysteresis to prevent cycling of the fans after the cooking appliances have been turned off and the heat
in the exhaust system is reduced. The hysteresis is factory set 2 degrees and will keep the exhaust running
until the temperature falls 2 degrees below the activation set point. The activation and hysteresis settings
may be field adjusted on the temperature controller inside the control enclosure to meet actual operating
conditions. The panel is factory pre-wired to shut down supply fans in a fire condition. There is also a
factory pre-wire option to turn the exhaust fans on in a fire condition (if required).
|
|
|
|