Rep Our Products

Are you interested in representing CaptiveAire and selling our products?
Please fill out the following form, and we will contact you soon.

This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.

 
Direct-Fired Formulas

Heating Requirements
Input BTU/Hr =   (Blower SCFM * Temp Rise * Density Factor) / .92


Temp Rise =   (Input BTU/Hr * .92)

Blower SCFM * Density Factor


Density Factor =   1.08 +  (70-Blower Temp) * .024

10



Output BTU/Hr
Output BTU/Hr =   Input BTU/Hr * .92



Profile Velocity
Profile Velocity =   945 * sqrt(Profile Pressure / 0.075)



Burner Areas
6 Inch Straight = .32 sq ft.
12 Inch Straight = .65 sq ft.
T Section = .77 sq ft.
Ell Section = .65 sq ft.